PENENTUAN KLORIN BEBAS PADA INDIRECT COOLING WATER

M.Taufik Eka Prasada

Abstract

Analysis of free chlorine for ten days of indirect oleo chemical cooling water sample has been carried out. Analysis of free chlorine using a colorimetric instrument based on the occurrence of color after using DPD powder. The concentration level of the color of the sample on the colorimeter showed the level of chlorine. The results of research conducted for 10 days showed that the free chlorine content in indirect cooling water samples were 0.28-0.42 ppm. Chlorine levels obtained in accordance with the recommended quality standard 0.3-0.5 ppm.

Keywords

free chlorine, indirect cooling water, colorimetric

Full Text:

PDF

References

Busyairi, M., Dewi, Y.P., dan Widodo,D.I., 2016, Efektivitas Kaporit Pada Proses Klorinasi Terhadap Penurunan Bakteri Coliform Dari Limbah Cair Rumah Sakit X Samarinda, J. MANUSIA DAN LINGKUNGAN, Vol. 23, No. 2, hal: 156-162.

Hardayanti, N., 2006, Studi Evaluasi Instalasi Pengolahan Air Bersih Untuk Kebutuhan Domestik Dan Non Domestik., Semarang: Universitas Diponegoro.

Hasan, A., 2006, Dampak Penggunaan Klorin, J.Tek.Ling.P3TLBPPT,BBPT,7(1), hal: 90-96.

Khadijah, Afni, Muantullah, 2017, Analisis Faktor-Faktor Kualitas dan Dampak Air Industri Terhadap Mesin Dan Kualitas Plat, Journal Industrial Servicess Vol. 3 No. 1a, hal 98-106.

Lestari, E., 2006, Pengaruh Bioksida Pengoksidasi Terhadap Pertumbuhan Mikroorganisme Pada Air Pendingin Sekunder RSG-GAS. Banten: ISSN, hal: 1978-8738.